Sign In | Join Free | My himfr.com
Home > Relay Test Set >

Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules

Kingsine Electric Automation Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules from wholesalers
     
    Buy cheap Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules from wholesalers
    • Buy cheap Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules from wholesalers

    Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules

    Ask Lasest Price
    Brand Name : KINGSINE
    Model Number : K2063i
    Certification : ISO9001,CE
    Price : Negotiale
    Payment Terms : T/T in advance,L/C
    Supply Ability : 50 sets/M
    Delivery Time : 15 working days
    • Product Details
    • Company Profile

    Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules

    • Universal Relay Test Applications
    • 6x35A & 4x310V independent high burden output channels
    • Lightweight, <20Kg
    • Inbuilt 9.7” True color TFT LCD with touch screen, numerical and shortcut keyboard, fully control with / without laptop
    • GPS / IRIG-B code synchronize end-to-end testing
    • Fully function KRT software testing modules
    • 3-Years guarantee of free repair and life-long maintenance
    • Free software upgrade
    • Optional function for energy calibration, 13 Channels Low-Level outputs etc

    Ordering Ref.

    ModelCurrent OutputsVoltage Outputs
    K20666×30A @ 450VA max / 3×60A @ 850VA max7×130V @ 75VA max
    K2066i6×35A @ 450VA max / 3×70A @ 850VA max7×310V @ 90VA max
    K20636×30A @ 450VA max / 3×60A @ 850VA max4×130V @ 75VA max
    K2063i6×35A @ 450VA max / 3×70A @ 850VA max4×310V @ 124VA max
    K20303×30A @ 450VA max4×130V @ 75VA max
    K2030i3×35A @ 450VA max4×310V @ 124VA max

    Characteristic

    • 10 Channels (4V + 6I) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 20x harmonics.
    • Variable battery simulator, DC 0-310V, 124Watts max.
    • Graphical test modules and templates for testing of various relays
    • Quick relay testing facility in Manual mode
    • Shot/Search/Check, Point & Click testing
    • RIO/XRIO import & export facility
    • Switch on to fault test(SOTF)
    • Power system model for dynamic testing
    • Inbuilt GPS / IRIG-B sync end-to-end testing
    • Online Vector display
    • Automatic test results assume
    • Automatic test report creation
    • Self-protect for wrong power supply up to 450V AC/DC input.
    • Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection

    Parameters

    Voltage Outputs
    Output Range & Power4×310 V ac (L-N)124 VA max each
    2×620 V ac (L-L)248 VA max each
    3×310 V dc (L-N)124 W max each
    Accuracy

    ±2 mV @ 0.2~2 V ac

    <0.07%Rd+0.03Rg Guar. @ 2~310V ac

    <0.03%Rd+0.01Rg Typ. @ 2~310V ac

    ±10mV @ 0.5 V~5 V dc

    ±0.5% @ 5 V~310 V dc

    Resolution1mV
    Distortion<0.1% Guar. / <0.05%Typ.
    Current Outputs
    Output Range & Power6×35A ac (L-N)450 VA max each
    3×70A ac (2L-N)850 VA max each
    1×180A ac (6L-N)1200 VA max
    3×20A dc (L-N)300W max each
    Accuracy

    ±1 mA @ 0.2A~0.5A ac

    <0.15%Rd+0.05Rg Guar. @ 0.5~35A ac

    <0.05%Rd+0.02Rg Typ. @ 0.5~35A ac

    ±5mA @ 0.2 A~1 A dc

    ±0.5% @ 1 A~20 A dc

    Resolution1mA
    Distortion<0.1% Guar. / <0.05%Typ.
    Frequency Output
    Range5~1000 Hz, 3KHz transient output
    Accuracy<1ppm @ 5~65 Hz
    <10ppm @ 65~450 Hz
    <20ppm @ 450~1000 Hz
    Resolution0.001 Hz
    Phase Output
    Range-360°~360°
    Accuracy<0.05° Typ. / <0.1° Guar.
    Resolution0.001°
    Aux. DC Voltage Source (Battery simulator)
    Range0~310V @ 124W max
    Binary Input
    Quantity8pairs
    Input Characteristics0~400Vdc / Potential free
    Time Resolution<0.1ms
    Max. Measuring TimeInfinite
    Debounce Time0~25ms
    Binary Output
    Quantity

    4pairs NO relay contacts

    (4paris semiconductors output optional)

    TypePotential free, software controlled
    Break Capacity

    Vmax:300Vac Imax:4A Pmax:1000VA

    Vmax:300Vdc Imax:4A Pmax:300W

    Synchronization
    Synchronization ModeGPS, SMA type antenna connector
    Harmonic
    Superimposed Numbers2~20times
    Power supply & Environment
    Nominal Input Voltage110/220/230Vac preselection
    Permissible Input Voltage

    +/-20%, Max 264Vac

    Self-protect and alarm if input voltage out of range

    Nominal Frequency50/60Hz
    Permissible Frequency45Hz~65Hz
    Power Consumption1500 VA max
    Connection TypeStandard AC socket 60320
    Operating Temperature-10℃~55℃
    Storage Temperature-25℃~70℃
    Humidity<95%RH, non-condensing
    Others
    PC ConnectionRJ45 Ethernet, 10/100/1000M
    Grounding Terminal4mm banana socket
    Weight20 Kg
    Dimensions(W x D x H)480×320×160(mm)

    Additional Information (Optional Modules)

    Low-Level outputs
    Quantity13 Channels, phoenix male type
    Voltage Outputs RangeAC 0~8V, DC 0~10V
    Current Outputs RangeNominal 2mA, 10mA max transient
    Output Power≥0.5VA
    Accuracy

    (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar.

    (0.8~8 Vrms): <0.02% Typ. / <0.05% Guar.

    Resolution0.25mV
    Energy Meter Calibration
    Sensor UsageMechanical meters / Electronic meters
    Sensor OutputHigh lever:>4.5V, Low level:<0.2V
    Pulse Input1 pulse input port
    Pulse Range500KHz pulse input Max.
    Pulse Output1 Transistor output